How far can it detect?

Detection distance comes down to hot spot size, lens, and pixels on target. Three pixels on the hot spot is the design basis for accurate temperature; the figures below are for a Flir A70.

Custom Zones and Thresholds for the Earliest Reliable Alarm

Alarm logic runs on the camera and is configured to the hazard. Define where to look, what counts as an alarm, and how each rule communicates with the fire alarm control panel or monitoring system, delivering early warning and fire alarm functionality from the same device.

Alarm Types

Choose the detection logic that best matches your application.

🌡

Absolute Threshold

The zone exceeds a set temperature.

↗

Rate of Rise

Temperature climbs faster than a set number of degrees per minute.

Δ

Delta

The zone runs hotter than a reference, such as a neighboring asset or the ambient temperature, by more than a set margin.

◎

Growing Hot Spot

The share of the zone above a temperature grows past a set percentage.

Alarm Zones

Customize monitoring areas and alarm behavior for individual hazards.

▣

Full Coverage or Individual Hazards

A zone can span the entire field of view or be drawn around one asset.

⊘

Inclusion and Exclusion Zones

Watch what matters; ignore heaters, reflective surfaces, or anything that should never trigger.

☰

Stacked Zones with Different Logic

Multiple zones can overlap, each with its own alarm type, setpoint, and output. Full-view zones can give an early supervisory signal at one temperature and a fire alarm at a higher one.

20

Up to 20 Zones per Camera

Each mapped to a dry-contact output or a network alarm.

Three Integration Pathways. One Camera.

One camera, three connections. The fire alarm pathway is the listed one; video and data are supplementary. Video can run through an on-site VMS server or, with no server at ll, through Flir Aura cloud monitoring.

⚠
Fire Alarm
Digital I/O

Alarms to the FACP

Connect the camera to the fire alarm control panel through digital inputs and outputs.

 
✓ Dry contacts: Alarm, Supervisory, Fault
✓ Listed addressable input modules on the SLC
✓ 24 V DC listed, supervised power
✓ Wiring and programming per FACP manufacturer, NFPA 72, and AHJ
▶
Video Monitoring
ONVIF

Video to the VMS

Stream thermal and visual video to your video management system, or monitor through Flir Aura.

 
✓ ONVIF Profile S/T: thermal and visual video, overlays, alarm events
✓ Flir Latitude or any ONVIF VMS
✓ No server? Flir Aura cloud provides web-based alarm handling, trending, and mobile alerts
⇄
Data Integration
Modbus TCP

Data and Alarms to SCADA

Share temperature measurements, alarm information, and diagnostics with industrial control systems.

 
✓ Temperatures, alarm status, event flags, diagnostics
✓ Polled or event-driven
✓ Any Modbus TCP master: SCADA, historian, BMS

Common applications for thermal imaging fire detection

 

Where the hazard produces heat long before smoke, and where high ceilings, airflow, dust, or outdoor exposure make conventional detection slow or impractical.

BESS Sites

24/7 indoor and outdoor monitoring of containers and enclosures; the detection layer NFPA 855 designs call for.

Learn more

Data Centers

UPS battery rooms, PDUs, and electrical infrastructure, where a fault is measurable in heat long before it produces smoke.

Learn more

Manufacturing

Process lines, electrical rooms, and product storage where heat buildup precedes ignition.

Learn more

Solar Fields and Rooftop Arrays

Inverter, combiner box, and panel-level hot spot detection across field and rooftop installations.

Learn more

Heavy Industrial

Forest products, pulp and paper, metals, and other heavy industrial sites where dust, airflow, and open structures defeat conventional detection.

Learn more

Warehousing & High-Bay Racking

Wide-area coverage of rack storage and automated storage and retrieval systems where ceiling-mounted detection is slow to respond.

Learn more

Waste and Recycling

Tipping floors, bunkers, conveyors, and bale storage, with alarms on the hot spot rather than the smoke plume.

Learn more

Power Substations

Where outdoor exposure, airflow, and large open areas can delay smoke or heat from reaching traditional detectors, limiting early warning of developing equipment problems.

Learn more

Early Fire Detection by the A70

 

  • 640 × 480 radiometric thermal imaging plus a 1280 × 960 visual camera for instant context at alarm

  • 35 mK thermal sensitivity and ±2°C accuracy, calibrated at every pixel

  • On-camera alarm logic with up to 20 regions of interest: threshold, rate-of-rise, delta, and area-percentage triggers

  • Alarm, supervisory, and fault dry-contact outputs to the fire alarm control panel; Modbus TCP, MQTT, Ethernet/IP, and ONVIF for SCADA, BMS, and VMS

  • 29°, 51°, and 95° lens options with 3 × 3 pixel detection distances to 125 m (410 ft)

  • IP66, 24 V DC or PoE, rated for indoor and outdoor installation

Detect faster. Respond smarter.

Thermal imaging allows you to design a system that detects threats, not just responds to them. FLIR's Axx Series is UL 2684 listed, prescriptive under NFPA 72, and supported by FLIR from layout through commissioning.

Questions we hear from engineers

Both models come in three fields of view: 29° for the longest reach, 51° as the general-purpose choice, and 95° for wide coverage at short range. The A70 is built for long-range and wide-area monitoring, giving the best detection at the greatest distance and the highest performance: EV fleet and bus depots, warehouses, large combustible piles, and other large hazards. The A40 is ideal for smaller or individual hazards and room monitoring: hydraulic pump units, pump rooms, electrical gear, battery charging stations. Both carry the same listing, alarm logic, and outputs.

No. Thresholds are configured by the installing contractor at commissioning behind a password-protected interface, documented in the acceptance record, and retested after any change.

The dry-contact alarm, supervisory, and fault outputs. Modbus TCP, MQTT, Ethernet/IP, and ONVIF are supplementary paths for SCADA, BMS, and VMS and are outside the listing.

From the Discover Center

Whitepaper

The Difference Between a Warning and a Write-Off: How Thermal Intelligence Is Changing Cotton Harvester Fire Prevention

Read More
Application Story

Early Fire Detection for Tough Outdoor Environments

Read More

A Smarter Approach to Industrial Fire Prevention with Thermal Intelligence

Read More
Fundamentals

Flir Solutions for Early Fire Detection (EFD)

Read More
Fundamentals

Mill Ladle Refractory Monitoring

Read More

Flir Helps Prevent Forest Fires in Southern Italy

Read More
Application Story

Powered by Flir: How FlameSmart is Redefining Fire Protection in Waste Facilities

Read More

 

Request Info

Optin

By submitting you agree to FLIR's privacy policy and cookie policy.